HomeMy WebLinkAboutOrdinance No. 09-1792
THE CITY OF THE COLONY, TEXAS
ORDINANCE NO. 09-1792
AN ORDINANCE OF THE CITY OF THE COLONY, TEXAS
AMENDING THE CODE OF ORDINANCES BY AMENDING
CHAPTER 6, ARTICLE I, SECTION 6-5.2, BY DELETING ALL
REFERENCES TO THE INTERNATIONAL ENERGY
CONSERV AT ION CODE, 2003 EDITION, AND THE
AMENDMENTS THERETO AND PROVIDING FOR THE
ADOPTION OF THE INTERNATIONAL ENERGY
CONSERVATION CODE, 2006 EDITION; PROVIDING
AMENDMENTS TO THE INTERNATIONAL ENERGY
CONSERVATION CODE, 2006 EDITION; PROVIDING A
SEVERABILITY CLAUSE; PROVIDING A REPEALING
CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING A
PENALTY FOR VIOLATION OF THIS ORDINANCE NOT TO
EXCEED THE SUM OF TWO THOUSAND DOLLARS ($2,000.00)
FOR EACH OFFENSE; AND PROVIDING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF THE
COLONY, TEXAS:
SECTION 1. That the Code of Ordinances of the City of The Colony, Texas be,
and the same is, hereby amended by amending Chapter 6, Article I, Section 6-5.2 by
deleting all references to the International Energy Conservation Code, 2003 Edition and
the amendments thereto and providing for the adoption the International Energy
Conservation Code, 2006 Edition with the appendices, and the amendments thereto,
which shall read as follows:
"ARTICLE 1. IN GENERAL
Sec. 6-5.2. International Energy Conservation Code, 2006 Edition adopted and
amended.
(a) Adoption. The International Energy Conservation Code, 2006 Edition
with the appendices, as published by the International Code Council is hereby
adopted by reference. Unless deleted, amended, expanded or otherwise changed
herein, all provisions of such code shall be fully applicable and binding.
(b) Amendments.
Page 1
TM 33473.76.000
Amend Section 101.4.2 Historic Buildings to read asfollows:
101.4.2 Historic Buildings. Any building or structure that is listed in the State or
National Register of Historic Places; designated as a historic property under local or state
designation law or survey; certified as a contributing resource with a National Register
listed or locally designated historic district; or with an opinion or certification that the
property is eligible to be listed on the National or State Registers of
Historic Places either individually or as a contributing building to a historic district by the
State Historic Preservation Officer of the Keeper of the National Register of Historic
Places, are exempt from shall comply with all of the provisions of this code.
Exception: Whenever a provision or provisions shall invalidate or ieopardize the
historical designation or listing, that provision or provisions may be exempted.
Amend Section 103.1.1 Above code programs, to read asfollows:
103.1.1 Alternative compliance. A building certified by a national, state, or local
accredited energy efficiency program and determined by the Energy Systems Laboratory
to be in compliance with the energy efficiency requirements of this section may, at the
option of the Code Official, be considered in compliance. The United States
Environmental Protection Agency's Energy Star Program certification of energy code
equivalency shall be considered in compliance.
Amend Section 202 GENERAL DEFINITIONS by adding the following definition:
GLAZING AREA. Total area of the glazed fenestration measured using the rough
opening and including sash, curbing or other framing elements that enclose conditioned
space. Glazing area includes the area of glazed fenestration assemblies in walls bounding
conditioned basements. For doors where the daylight opening area is less that 50 percent
of the door area, the glazing area is the daylight opening area. For all other doors, the
glazing area is the rough opening area for the door including the door and the frame.
Amend Section 301.1 to read asfollows:
301.1 General. Climate zones from Figure 301.1, Figure 301.2, ef Table 301.1(1), Table
301.2(1), or Table 301.3(3) shall be used in determining the applicable requirements from
Chapters 4 & 5. Locations not in Table 301.1 (outside the US) shall be assigned a climate
zone based on Section 301.3.
Page 2
TM 33473.76.000
Add FIGURE 301.2 -TEXAS CLIMATE ZONES immediately following Figure 301.1:
DRY (8)
MOIST (A)
..
..
_ 4
_ 34
_3.3
D 3:2
_ 3.1
- :2:2
_ :21
..-
FIGURE 301.2: TEXAS CLIMATE ZONES
Page 3
TM 33473.76.000
Amend TABLE 301.1 by deleting the references to Texas and add TABLE 301.1(1)
CLIMATE ZONES AND SUB CLIMATE ZONES FOR TEXAS:
TABLE 301.1(1) CLIMATE ZONES AND SUB CLIMATE ZONES FOR TEXAS
Zone 2
ANDERSON 2.2 DE WITT 2.1 JIM HOGG 2.1 ORANGE 2.2
ANGELINA 2.2 DIMMIT 2.1 JIM WELLS 2.1 POLK 2.2
ARANSAS 2.1 DUVAL 2.1 KARNES 2.1 REAL 2.2
ATASCOSA 2.1 EDW ARDS 2.2 KENEDY 2.1 REFUGIO 2.1
AUSTIN 2.2 FALLS 2.2 KINNEY 2.2 ROBERTSON 2.2
BANDERA 2.2 FAYETTE 2.2 KLEBERG 2.1 SAN JACINTO 2.2
BASTROP 2.2 FORT BEND 2.2 LA SALLE 2.1 SAN PATRICIO 2.1
BEE 2.1 FREESTONE 2.2 LAVACA 2.2 STARR 2.1
BELL 2.2 FRIO 2.1 LEE 2.2 TRAVIS 2.2
BEXAR 2.2 GALVESTON 2.1 LEON 2.2 TRINITY 2.2
BOSQUE 2.2 GOLIAD 2.1 LIBERTY 2.2 TYLER 2.2
BRAZORIA 2.1 GONZALES 2.2 LIMESTONE 2.2 UVALDE 2.2
BRAZOS 2.2 GRIMES 2.2 LIVE OAK 2.1 VAL VERDE 2.2
BROOKS 2.1 GUADALUPE 2.2 MADISON 2.2 VICTORIA 2.1
BURLESON 2.2 HARDIN 2.2 MATAGORDA 2.1 WALKER 2.2
CALDWELL 2.2 HARRIS 2.2 MAVERICK 2.1 WALLER 2.2
CALHOUN 2.1 HAYS 2.2 MCLENNAN 2.2 WASHINGTON 2.2
CAMERON 2.1 HIDALGO 2.1 MCMULLEN 2.1 WEBB 2.1
CHAMBERS 2.2 HILL 2.2 MEDIN A 2.2 WHARTON 2.1
CHEROKEE 2.2 HOUSTON 2.2 MILAM 2.2 WILLACY 2.]
COLORADO 2.2 JACKSON 2.1 MONTGOMERY 2.2 WILLIAMSON 2.2
COMAL 2.2 JASPER 2.2 NEWTON 2.2 WILSON 2.2
CORYELL 2.2 JEFFERSON 2.2 NUECES 2.1 ZAPATA 2.1
Zone 3
ANDREWS 3.2 EL PASO 3.2 KERR 3.1 ROCKW ALL 3.2
ARCHER 3.3 ELLIS 3.2 KIMBLE 3.1 RUNNELS 3.2
BAYLOR 3.3 ERATH 3.2 KING 3.3 RUSK 3.2
BLANCO 3.1 FANNIN 3.2 KNOX 3.3 SABINE 3.2
BORDEN 3.3 FISHER 3.2 LAMAR 3.2 SAN AUGUSTINE 3.2
BOWIE 3.2 FOARD 3.3 LAMPASAS 3.2 SAN SABA 3.2
BREWSTER 3.1 FRANKLIN 3.2 LLANO 3.1 SCHLEICHER 3.1
BROWN 3.2 GAINES 3.3 LOVING 3.2 SCURRY 3.3
BURNET 3.1 GARZA 3.3 LUBBOCK 3.3 SHACKELFORD 3.2
CALLAHAN 3.2 GILLESPIE 3.1 LYNN 3.3 SHELBY 3.2
CAMP 3.2 GLASSCOCK 3.2 MARION 3.2 SMITH 3.2
CASS 3.2 GRAYSON 3.2 MARTIN 3.2 SOMERVELL 3.2
CHILDRESS 3.3 GREGG 3.2 MASON 3.1 STEPHENS 3.2
CLAY 3.3 HALL 3.4 MCCULLOCH 3.2 STERLING 3.2
COKE 3.2 HAMILTON 3.2 MENARD 3.1 STONEWALL 3.3
COLEMAN 3.2 HARDEMAN 3.3 MIDLAND 3.2 SUTTON 3.1
COLLIN 3.2 HARRISON 3.2 MILLS 3.2 TARRANT 3.2
COLLINGSWORTH 3.3 HASKELL 3.2 MITCHELL 3.2 TAYLOR 3.2
COMANCHE 3.2 HEMPHILL 3.4 MONTAGUE 3.2 TERRELL 3.1
CONCHO 3.2 HENDERSON 3.2 MORRIS 3.2 TERRY 3.3
COOKE 3.2 HOOD 3.2 MOTLEY 3.3 THROCKMORTON 3.2
COTTLE 3.3 HOPKINS 3.2 NACOGDOCHES 3.2 TITUS 3.2
CRANE 3.2 HOWARD 3.2 NAVARRO 3.2 TOM GREEN 3.2
CROCKETT 3.1 HUDSPETH 3.2 NOLAN 3.2 UPSHUR 3.2
CROSBY 3.3 HUNT 3.2 PALO PINTO 3.2 UPTON 3.2
CULBERSON 3.2 IRION 3.2 PANOLA 3.2 V AN ZANDT 3.2
Page 4
TM 33473.76.000
DALLAS 3.2 JACK 3.2 PARKER 3.2 WARD 3.2
DAWSON 3.3 JEFF DAVIS 3.2 PECOS 3.2 WHEELER 3.4
DELTA 3.2 JOHNSON 3.2 PRESIDIO 3.] WICHITA 3.3
DENTON 3.2 JONES 3.2 RA]NS 3.2 WILBARGER 3.3
DICKENS 3.3 KAUFMAN 3.2 REAGAN 3.2 WINKLER 3.2
EASTLAND 3.2 KENDALL 3.1 RED RIVER 3.2 WISE 3.2
ECTOR 3.2 KENT 3.3 REEVES 3.2 WOOD 3.2
YOUNG 3.2
Zone 4
ARMSTRONG DEAF SMITH HOCKLEY PARMER
BAILEY DONLEY HUTCHINSON POTTER
BRISCOE FLOYD LAMB RANDALL
CARSON GRAY LIPSCOMB ROBERTS
CASTRO HALE MOORE SHERMAN
COCHRAN HANSFORD OCHIL TREE SWISHER
DALLAM HARTLEY OLDHAM YOAKUM
Amend TABLE 301.2 by deleting the references to Texas and add TABLE 301.2(1)
WARM HUMID COUNTIES FOR TEXAS
TABLE 301.2(1) WARM HUMID COUNTIES FOR TEXAS
ANDERSON 2.2 DUVAL 2.1 KAUFMAN 3.2 RED RIVER 3.2
ANGELINA 2.2 EDW ARDS 2.2 KENDALL 3.1 REAL 2.2
ARANSAS 2.1 ELLIS 3.2 KENEDY 2.1 REFUGIO 2.1
ATASCOSA 2.1 ERATH 3.2 KINNEY 2.2 ROBERTSON 2.2
AUSTIN 2.2 FALLS 2.2 KLEBERG 2.1 ROCKW ALL 3.2
BANDERA 2.2 FAYETTE 2.2 LA SALLE 2.1 RUSK 3.2
BASTROP 2.2 FORT BEND 2.2 LAMAR 3.2 SABINE 3.2
BEE 2.1 FRANKLIN 3.2 LAMPASAS 3.2 SAN AUGUSTINE 3.2
BELL 2.2 FREESTONE 2.2 LAVACA 2.2 SAN JACINTO 2.2
BEXAR 2.2 FRIO 2.1 LEE 2.2 SAN PATRICIO 2.1
BLANCO 3.1 GALVESTON 2.1 LEON 2.2 SAN SABA 3.2
BOSQUE 2.2 GILLESPIE 3.1 LLANO 3.1 SHELBY 3.2
BOWIE 3.2 GOLIAD 2.1 LIBERTY 2.2 SMITH 3.2
BRAZORIA 2.1 GONZALES 2.2 LIMESTONE 2.2 STARR 2.1
BROWN 3.2 GREGG 3.2 LIVE OAK 2.1 SOMMERVELL 3.2
BRAZOS 2.2 GRIMES 2.2 MADISON 2.2 TARRANT 3.2
BROOKS 2.1 GUADALUPE 2.2 MARION 3.2 TITUS 3.2
BURLESON 2.2 HAMILTON 3.2 MATAGORDA 2.1 TRAVIS 2.2
BURNET 3.1 HARDIN 2.2 MAVERICK 2.1 TRINITY 2.2
CALDWELL 2.2 HARRIS 2.2 MCLENNAN 2.2 TYLER 2.2
CALHOUN 2.1 HARR]SON 3.2 MCMULLEN 2.1 UPSHUR 3.2
CAMERON 2.1 HAYS 2.2 MEDINA 2.2 UVALDE 2.2
CHAMBERS 2.2 HENDERSON 3.2 MILAM 2.2 VAL VERDE 2.2
CAMP 3.2 HIDALGO 2.1 MILLS 3.2 V AN ZANDT 3.2
CASS 3.2 HOOD 3.2 MONTGOMERY 2.2 V]CTORIA 2.1
CHEROKEE 2.2 HOPKINS 3.2 MORRIS 3.2 WALKER 2.2
COLLIN 3.2 HILL 2.2 NACOGDOCHES 3.2 WALLER 2.2
COLORADO 2.2 HOUSTON 2.2 NAVARRO 3.2 WASHINGTON 2.2
CO MAL 2.2 HUNT 3.2 NEWTON 2.2 WEBB 2.1
COMANCHE 3.2 JACKSON 2.1 NUECES 2.1 WHARTON 2.1
CORYELL 2.2 JASPER 2.2 ORANGE 2.2 WILLACY 2.1
DALLAS 3.2 JEFFERSON 2.2 PALO PINTO 3.2 WILLIAMSON 2.2
DELTA 3.2 JIM HOGG 2.1 PANOLA 3.2 WILSON 2.2
Page 5
TM 33473.76.000
DENTON
DE WITT
DIMMIT
3.2 JIM WELLS
2.1 JOHNSON
2.1 KARNES
2.1 PARKER
3.2 POLK
2.1 RAINS
3.2 WOOD
2.2 ZAPATA
3.2 ZAVALA
3.2
2.1
2.1
Add Section 401.2.1. Compliance software tools. to read asfollows:
401.2.1. Compliance software tools. Software tools used to demonstrate energy code
compliance that are deemed acceptable by the building official. The PNL program RES
Check is not acceptable for residential compliance.
Amend Section 402.1.1 Insulation and fenestration criteria. to read as follows:
402.1.1 Insulation and fenestration criteria. The building thermal envelope shall meet
the requirements of Table 402.1.1 based on the climate zone specified in Chapter 3. The
use of REScheck⢠shall not be an acceptable means of demonstrating envelope
compliance.
When compliance using Table 402.1.1 is demonstrated with a ceiling R-value ofR30 or
less, no more than 33% of the total projected ceiling area may be of cathedral type
construction (ceiling joist/roof rafter assembly) and the required insulation R-value may
be reduced to a minimum of R22 insulation when the remaining ceiling area insulation is
increased to R38.
Replace TABLE 402.1.1 INSULATION AND FENESTRATION REQUIREMENTS
BY COMPONENT to read as follows:
MAX
GLAZED MASS
CLIMATE AREA TO MAX MAX WALL MIN MIN MIN
-SUB WALL GLAZED SKYLIGHT MAX GLAZED MIN MIN WOOD R- FLOOR BASEMENT MIN SLAB CRAWL SPACE
CLIMATE AREA FENESTRATION V- FENESTRATION CEILING FRAME WALL VALUE R- WALL R-VALUE WALL
ZONE RATIO V-FACTOR FACTORb SHGC R-VALUE R-VALUEd VALUE R-VALUE & DEPTW R-VALUE
15 0.75 0.75 0.38 19 13 6 19 0 0 5
20 0.70 0.75 0.38 30 13 6 19 0 0 5
2.1
25 0.65 0.75 0.35 30 13 6 19 0 0 5
30 0.54 0.75 0.35 38 13 6 19 0 0 5
15 0.65 0.75 0.38 30 13 6 19 5 0 6
20 0.65 0.75 0.38 38 ]3 6 19 6 0 6
2.2 25 0.54 0.75 0.35 38 13 6 19 8 0 10
30 0.46 0.75 0.35 38 16,13+3.7" 6 19 8 0 10
15 0.65 0.65 0.40 30 13 6 19 5 0 6
20 0.55 0.65 0.40 38 13 6 19 5 0 6
3.1 25 0.54 0.65 0.35 38 13 6 19 8 0 10
30 0.46 0.65 0.35 38 16,13+3.7" 7 19 8 0 10
15 0.60 0.65 0.40 30 13 6 19 6 0 7
20 0.54 0.65 0.40 38 13 6 19 6 0 7
3.2 25 0.51 0.65 0.40 38 16,13+3.7" 7 19 6 0 7
30 0.46 0.65 0.38 38 16,13+3.7" 7 ]9 6 0 7
TABLE 402.1.1
INSULA TION AND FENESTRATION REQUIREMENTS BY COMPONENT (TEXAS)8
Page 6
TM 33473.76.000
15 0.51 0.65 0.40 30 13 6 19 7 0 8
20 0.45 0.65 0.40 38 13 6 19 7 0 9
3.3 25 0.40 0.65 0.40 38 16,13+3.7" 7 19 7 0 9
30 0.40 0.65 0.40 38 19, 13 + 8.1e 9 19 7 0 9
15 0.45 0.60 NR 38 13 6 19 8 5,2 ft 11
20 0.37 0.60 NR 38 13 6 19 8 6,2 fI 13
3.4 25 0.37 0.60 NR 38 19,13 + 8.1" 9 19 8 6,2 ft 13
30 0.37 0.60 NR 38 19,13+8.1e 9 30 8 6,2 ft 13
]5 0.45 0.60 NR 38 13 8 19 8 5,2 ft 11
20 0.37 0.60 NR 38 13 8 19 9 6,2 ft 13
4 25 0.37 0.60 NR 38 19,13+8.1e 10 19 9 6,2 ft 13
30 0.37 0.60 NR 38 19,13 + 8.1e 10 30 9 6,2 ft 13
For SI: 1 foot = 304.8 mm.
a. R-values are minimums. U-factors and SHGC are maXImums. R-19 shall be
permitted to be compressed into a 2 X 6 cavity.
b. The fenestration U-factor column excludes skylights. The SHGC column applies
to all glazed fenestration.
c. R-5 shall be added to the required slab edge R-values for heated slabs.
d. The total R-value may be achieved with a combination of cavity insulation and
insulating sheathing that covers 100% of the exterior wall.
e. The wall insulation may be the sum of the two values where the first value is the
cavity insulation and the second value is insulating sheathing. The combination
of cavity insulation plus insulating sheathing may be used where structural
sheathing covers not more than 25% of the exterior wall area and insulating
sheathing is not required where structural sheathing is used. If structural
sheathing covers more than 25% of exterior wall area then the wall insulation
requirement may only be satisfied with the single insulation value.
Page 7
TM 33473.76.000
Replace TABLE 402.1.3 EQUIVALENT U-FACTORS to read asfollows:
TABLE 402.1.3
EQUIVALENT U-F ACTORSa
MAX MAX
GLAZED MAX CRAWL
CLIMATE - AREA TO MAX MAX WOOD MASS MAX MAX SPACE
SUB WALL GLAZED MAX MAX FRAME WALL FLOOR BASEMENT WALL
CLIMATE AREA FENESTRATION SKYLIGHT CEILING WALL V- V- WALL V-
ZONE RATIO V FACTOR V-FACTOR V-FACTOR V-FACTOR FACTOR FACTOR V-FACTOR FACTOR
15 0.75 0.75 0.039 0.082 0.124 0.047 0.360 0.1 36
20 0.70 0.75 0.034 0.082 0.124 0.047 0.360 0.136
2.1 25 0.65 0.75 0.034 0.082 0.124 0.047 0.360 0.136
30 0.54 0.75 0.030 0.082 0.124 0.047 0.360 0.136
15 0.65 0.75 0.034 0.082 0.1 24 0.047 0.210 0.]00
20 0.65 0.75 0.030 0.082 0.124 0.047 0.210 0.100
2.2 25 0.54 0.75 0.030 0.082 0.124 0.047 0.119 0.065
30 0.46 0.75 0.030 0.071 0.124 0.047 0.119 0.065
15 0.65 0.65 0.034 0.082 0.124 0.047 0.210 0.100
20 0.55 0.65 0.030 0.082 0.1 24 0.047 0.210 0.100
3.1 25 0.54 0.65 0.030 0.082 0.1 24 0.047 0.119 0.065
30 0.46 0.65 0.030 0.071 0.112 0.047 0.119 0.065
15 0.60 0.65 0.034 0.082 0.1 24 0.047 0.179 0.075
20 0.54 0.65 0.030 0.082 0.1 24 0.047 0.179 0.075
3.2 0.51 0.65 0.030 0.071 0.112 0.047 0.1 79 0.075
25
30 0.46 0.65 0.030 0.071 0.112 0.047 0.1 79 0.075
15 0.51 0.65 0.034 0.082 0.124 0.047 0.149 0.061
20 0.45 0.65 0.030 0.082 0.124 0.047 0.149 0.058
3.3 25 0.40 0.65 0.030 0.075 0.112 0.047 0.149 0.058
30 0.40 0.65 0.030 0.061 0.094 0.047 0.149 0.058
15 0.45 0.60 0.030 0.082 0.124 0.047 0.119 0.083
20 0.37 0.60 0.030 0.082 0.124 0.047 0.119 0.152
3.4 25 0.37 0.60 0.030 0.061 0.094 0.047 0.119 0.152
30 0.37 0.60 0.030 0.061 0.094 0.033 0.1]9 0.152
15 0.45 0.60 0.030 0.082 0.1 02 0.047 0.119 0.083
4 20 0.37 0.60 0.030 0.082 0.102 0.047 0.089 0.152
25 0.37 0.60 0.030 0.061 0.087 0.047 0.089 0.152
30 0.37 0.60 0.030 0.061 0.087 0.033 0.089 0.152
a. Nonfenestration V-factors shall be obtained from measurement, calculation or an approved source.
Add Section 402.2.11. Insulation installed in walls. to read asfollow:
Section 402.2.11. Insulation installed in walls. Insulation batts installed in walls shall
be totally surrounded by an enclosure on all sides consisting of framing lumber, gypsum,
sheathing, wood structural panel sheathing or other equivalent material approved by the
building official.
Amend Section 402.3.2 Glazedfenestration SHGC. to read asfollows:
402.3.2 Glazed fenestration SHGC. An area-weighted average of fenestration products
more than 50 percent glazed shall be permitted to satisfy the SHGC requirements. In sub
climate zones 2.1, 2.2, 3.1, 3.2 and 3.3 the maximum area-weighted average and the
maximum SHGC shall not exceed 0.40.
Page 8
TM 33473.76.000
Amend Section 402.3.3 Glazedfenestration exemption. to read asfollows:
402.3.3 Glazed fenestration exemption. Up to 15 square feet (1.1 m;1j 1 percent of
glazed fenestration per dwelling unit shall be permitted to be exempt from U-factor and
SHGC requirements in Section 402.1.1.
Amend Section 402.3.5 Thermally isolated sunroom U-factor. to read as follows:
Section 402.3.5 Thermally isolated sunroom U faetor. For zones 1 through 8, the
maximum fenestration U factor shall be 0.50 and the maximum skylight U factor shall be
~ New windows and doors separating the sumoom from conditioned space shall meet
the building thermal envelope requirements.
Amend Section 402.3.6 Replacementfenestration. to read asfollows:
Section 402.3.6 Replacement fenestration. Where some or all of an eXIstmg
fenestration unit is replaced with a new fenestration product, including sash and glazing,
the replacement fenestration unit shall meet the applicable requirements for U-factor aae
SHGC in Table 102.1.1 402.3.7.
Exceptions:
.L Replacement skylights shall have a maximum U-factor for 0.60 when installed
in all sub climate zones except for 2.1.
2. For buildings constructed in conformance with an energy code as required by
State of Texas Senate Bill Number 5, 7ih Legislature, replacement fenestration
units may comply with the original construction documents or applicable U-
factor in Table 402.1.1.
Add Section 402.3.7 Prescriptive path for additions. to read as follows:
Section 402.3.7 Prescriptive path for additions. As an alternative for demonstrating
compliance, additions with a conditioned floor area less than 500 square feet (46.5 m2) to
existing single-family residential buildings and structures shall meet the prescriptive
envelope component criteria in Table 402.3.7 for the sub climate zone applicable to the
location. The U-factor of each individual fenestration product (windows, doors and
skylights) shall be used to calculate and area-weighted average fenestration product U-
factor for the addition, which shall not exceed the applicable listed values in Table
402.3.7. For additions, other than sumoom additions, the total area of fenestration
products shall not exceed 40 percent of the gross wall and roof area of the addition. The
R-values for opaque thermal envelope components shall be equal to or greater than the
applicable listed values in Table 402.3.7.
Conditioned sumoom additions shall maintain thermal isolation; shall not be used as
kitchens or sleeping rooms.
Page 9
TM 33473.76.000
In sub climate zones 2.1, 2.2, 3.1, 3.2 and 3.3, the combined solar heat gain coefficient
(the area weighted average) of all glazed fenestration products used in additions and as
replacement windows in accordance with this section shall not exceed 0.40.
Add Table 402.3.7 PRESCRIPTIVE ENVELOPE COMPONENT CRITERIA
ADDITIONS TO AND REPLACEMENT WINDOWS FOR EXISTING DETACHED
ONE- AND TWO-FAMILY DWELLINGS to read as follows:
Table 402.3.7 PRESCRIPTIVE ENVELOPE COMPONENT CRITERIA
ADDITIONS TO AND REPLACEMENT WINDOWS FOR EXISTING DETACHED
ONE- AND TWO-FAMILY DWELLINGSd
MAXIMUM MINIMUM
SUB Slab
CLIMATE Fenestration Ceiling Basement wall perimeter R- Crawl space
ZONES V-factor R-va1uea.e Wall R-va1uee Floor R-va1ue R-valueb value wall R-value
2.1 0.75 R-26 R-13 R-ll R-5 R-O R-5
2.2,3.1,3.2, 0.50 R-30 R-13 R-I9 R-8 R-O R-IO
3.3 and 3.4
4 0.50 R-38 R-I3 R-2I R-IO R-O R-I9
a. "Ceiling R-value" shall be required for flat or inclined (cathedral) ceilings. Floors over
outside air shall meet "Ceiling R-value" requirements.
b. Basement wall insulation to be installed in accordance with Section 402.2.6.
c. "Crawl space wall R-value" shall apply to unventilated crawl spaces only. Crawl space
insulation shall be installed in accordance with Section 402.2.8.
d. Sunroom additions shall be required to have a maximum fenestration V-factor of 0.5. in
all sub climate zones except sub climate zone 2.1. In all sub climate zones, the minimum
ceiling R-value for sunroom additions shall be R-19 and the minimum wall R-value shall
be R-13.
Add Exception No.2. to Section 403.2.1. Insulation to read asfollows:
Section 403.2.1. Insulation. Supply and return ducts shall be insulated to a minimum of
R-8. Ducts in floor trusses shall be insulated to a minimum of R-6.
Exceptions:
1. Ducts or portions thereof located completely inside the building
thermal envelope.
2. Supply and return ducts can be insulated to a minimum of R-6, if the
efficiency of the cooling equipment is upgraded to one SEER point
above the NAECA (National Appliance Energy Conservation Act)
Standard.
Add Section 501.3. Compliance software tools. to read asfollows:
Section 501.3. Compliance software tools. Software tools used to demonstrate energy
code compliance that are deemed acceptable by the building official may only utilize the
energy chapter of the 2006 International Energy Conservation Code or the 2004 Edition
of AHSRAE 90.1 Energy Standard for Buildings Except Low-rise Residential Buildings
Page 10
TM 33473.76.000
when code edition and/or standard selection is available.
Amend Section 505.2.1 Interior Lighting Controls. to read as follows:
505.2.1 Interior lighting controls. Each area enclosed by walls or floor-to-ceiling
partitions shall have at least one manual control for the lighting serving that area. The
required controls shall be located within the area served by the controls or be a remote
switch that identifies the lights served and their status. Each control device shall control
a maximum of 2,500 square feet (232.26 square meters) of floor area for a space 10,000
square feet (929.03 square meters) or less and a maximum of 10,000 square feet (929.03
square meters) for a space greater than 10,000 square feet (929.03 square meters).
"
SECTION 2. If any section, subsection, paragraph, sentence, phrase or work in
this ordinance, or application thereof to any person or circumstance is held invalid by any
court of competent jurisdiction, such holding shall not affect the validity of the remaining
portions of this ordinance, and the City Council of the City of The Colony, Texas hereby
declares it would have enacted such remaining portions despite any such invalidity.
SECTION 3. That the repeal of any ordinance or any portion thereof by the
preceding sections shall not affect or impair any act done or right vested or accrued or
any proceeding, suit or prosecution had or commenced in any cause before such repeal
shall take effect; but every such act done, or right vested or accrued, or proceedings, suit
or prosecution had or commenced shall remain in full force and effect to all intents or
purposes as if such ordinance or part thereof so repealed shall remain in force.
SECTION 4. That any person, firm or corporation violating any of the
provisions of this ordinance or the Code of Ordinances as amended hereby, shall be
guilty of a misdemeanor and upon conviction in the Municipal Court of the City of The
Colony, Texas, shall be subject to a fine not to exceed the sum of Two Thousand Dollars
($2,000.00) for each offense; and each and every day such offense is continued shall
constitute a new and separate offense.
SECTION 5. That this ordinance shall become effective immediately from and
after its passage and the publication of the caption, as the law and charter in such cases
provide.
PASSED AND APPROVED by the City Council of the City of The Colony,
Texas, this the 19th day of January, 2009.