HomeMy WebLinkAboutOrdinance No. 07-1718
CITY OF THE COLONY, TEXAS
ORDINANCE NO. 07-1718
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF THE
COLONY, TEXAS, AMENDING CHAPTER 12, ARTICLE IX, BY
REPEALING SECTIONS 12-151 THROUGH 12-190 OF THE CODE OF
ORDINANCES AND PROVIDING FOR A NEW CHAPTER 12,
ARTICLE IX OF THE CODE OF ORDINANCES SECTIONS 12-151
THROUGH 12-171 RELATING TO CROSS CONNECTION CONTROL
AND PREVENTION; PROVIDING FOR DEFINITIONS;
PROVIDING FOR CROSS CONNECTIONS STANDARDS;
PROVIDING FOR RIGHT-OF-WAY ENCROACHMENT;
PROVIDING FOR MULTIPLE CONNECTIONS; PROVIDING
REQUIREMENT FOR PROTECTION/INSTALLATION;
PROVIDING FOR TESTING OF ASSEMBLIES; PROVIDING
FOR THERMAL EXPANSION; PROVIDING FOR PRESSURE
LOSS; PROVIDING FOR RESIDENTIAL SERVICE
CONNECTIONS; PROVIDING FOR RENTAL PROPERTIES;
PROVIDING FOR CUSTOMER SERVICE INSPECTION;
PROVIDING INSTALLATION GUIDELINES AND
REQUIREMENTS FOR BACKFLOW PREVENTION
ASSEMBLIES; PROVIDING FOR AIR GAP SEPARATION;
PROVIDING FOR FIRE SUPPRESSION SYSTEMS;
PROVIDING FOR FIRE HYDRANT PROTECTION;
PROVIDING RESPONSIBILITIES OF PROPERTY OWNER
CLAUSE; PROVIDING FOR BACKFLOW PREVENTION
ASSEMBLY TESTER CERTIFICATION AND REGISTRATION;
PROVIDING FOR FEES; PROVIDING FOR COMPLIANCE
FOR LAWN IRRIGATION; PROVIDING FOR MOBILE UNITS;
PROVIDING FOR ENFORCEMENT; RESERVING SECTIONS
12-172 THROUGH 12-190 FOR FUTURE USE; PROVIDING A
SEVERABILITY CLAUSE; PROVIDING A SAVINGS CLAUSE;
PROVIDING A PENALTY CLAUSE OF A FINE NOT TO EXCEED
FIVE HUNDRED DOLLARS ($500) FOR EACH OFFENSE; AND
PROVIDING AN EFFECTIVE DATE.
WHEREAS, the City of The Colony, located in Denton County, Texas, is a Horne
Rule municipality possessing the full power of local self-government as provided by Article
XI, Section 5 of the Constitution of the State of Texas, Section 51.072 of the Texas Local
Government Code and its Horne Rule Charter; and
WHEREAS, The City Council of the City of The Colony, Texas (hereinafter referred to
as "the City") is the ultimate repository of authority in the City and is empowered under the
Texas Local Government Code, Section 51.001, and its City Charter to pass ordinances,
rules, and regulations not inconsistent with the Constitution of the State of Texas and for the
good government, peace and order of the City, and the trade and commerce of the City;
WHEREAS, it is the desire of the City Council to further protect the potable water
supply of the City; and
WHEREAS, the City Council of the City deems it necessary and expedient to
make certain amendments to the Code of Ordinances as adopted by Ordinance No. 02-1405 on
October 7, 2002.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE
CITY OF THE COLONY, TEXAS:
SECTION 1. That the Code of Ordinances be, and the same is, hereby amended by
amending Chapter 12, Article IX, by repealing Sections 12-151 through 12-190 in its
entirety and replacing with a new Chapter 12, Article IX, CROSS CONNECTION
CONTROL AND PREVENTION, Sections 12-151 through 12-171, and by reserving
Sections 12-172 through 12-190 for future use, which shall read as follows:
"ARTICLE IX. CROSS CONNECTION CONTROL AND PREVENTION
Sec. 12-151. Definitions.
The following words, terms and phrases, when used in this article, shall have the
meanings ascribed to them in this section, except where the context clearly indicates a different
meanmg:
Air gap shall mean a physical separation between the free flowing discharge end of a
potable water supply piping and/or appurtenance and an open or nonpressure receiving vessel,
plumbing fixture or other device. An approved air-gap separation shall be at least twice the
diameter of the supply pipe measured vertically above the overflow rim of the vessel, plumbing
fixture or other device, and in no case shall be less than one inch.
Atmospheric vacuum breaker backflow prevention device or atmospheric vacuum
breaker or A VB shall mean a device used to prevent back-siphonage in nonhealth hazard
conditions. This device cannot be tested and cannot prevent backpressure backflow.
Auxiliary supply shall mean any water source or system other than the public water
system that may be available in the building or on the property, including ground water or
surface waters used for industrial, irrigation or any other purpose.
Bacliflow shall mean the flow in the direction opposite to the normal flow or the
introduction of any foreign liquids, gases, or substances into the water system of the city's water.
Bacliflow prevention assembly or assembly shall mean an assembly to counteract back
pressure or prevent backsiphonage.
Page 2
HI17I1Ub.IJIJIJ
Backpressure shall mean any elevation of pressure in the downstream piping system, by
any means, above the supply pressure at the point of consideration which would cause, or tend to
cause, a reversal of the normal direction of flow and the introduction of fluids, mixtures or
substances from any source other than the intended source.
Backsiphonage shall mean the flow of water or other liquids, mixtures or substances into
the distribution pipes of a potable water supply system from any source other than its intended
source caused by a sudden reduction of pressure in the potable water supply system.
Boresight or boresight to daylight shall mean providing adequate drainage for backflow
prevention assemblies installed in vaults through the use of an unobstructed drainpipe.
Commercial establishment shall mean any property or location which is not defined as
residential.
Contaminants shall mean any foreign material, solid or liquid, not common to the potable
water supply which makes the water unfit or undesirable for human or animal consumption.
Contamination means the admission of contaminants into the potable water supply
system.
Cross connection under this article shall mean any connection, physical or otherwise,
between a potable water supply system and any plumbing fixture or any tank, receptacle,
equipment or device, through which it is possible for any nonpotable, used, unclean, polluted and
contaminated water, or other substances, to enter into any part of such potable water system
under any condition or set of conditions.
Cross connection control device shall mean any nationally approved or recognized device
placed upon any connection, physical or otherwise, between a potable water supply system and
any plumbing fixture or any tank, receptacle, equipment or device, which is designed to prevent
nonpotable, used, unclean, polluted and contaminated water, or other substances, from entering
into any part of such potable water system under any condition or set of conditions.
Cross connection customer service inspection shall mean an inspection designed to
inspect and detect any actual or potential cross connection hazards and/or any excess of the lead
action level in solder or flux, pipe or pipe fittings.
Degree of hazard shall mean the low or high hazard classification that shall be attached
to all actual or potential cross connections as determined by the most recently adopted
International Plumbing Code, as amended, and defined as follows:
(a) Health hazard means an actual or potential threat of contamination' of a physical or
toxic nature to the public potable water system or the consumer's potable water
system that would be a danger to health.
Page 3
nI17116.7b.IJIJIJ
(b) High hazard means the classification assigned to an actual or potential cross
connection that potentially could allow a substance that may cause illness or death
to backflow into the potable water supply.
( c) Low hazard means the classification assigned to an actual or potential cross
connection that potentially could allow a substance that may be objectionable but
not hazardous to one's health to backflow into the potable water supply.
(d) Pollution hazard means an actual or potential threat to the physical properties of the
water system or the potability of the public or the consumer's potable water system
but which would not constitute a health or system hazard, as defined. Maximum
degree of intensity of pollution which the potable water system could be degraded
under this definition would cause a nuisance or be aesthetically objectionable or
could cause damage to the system or its appurtenances.
(e) System hazard means an actual or potential threat of severe danger to the physical
properties of the public or consumer's potable water supply or of a pollution or
contamination that would have a detrimental effect on the quality of the potable
water in the system.
Double check detector bacliflow prevention assembly or double check
detector or DCDA shall mean an assembly composed of a line-size approved double check
assembly with a bypass containing a specific water meter and an approved double check valve
assembly. The meter shall register accurately for very low rates of flow.
Double check valve bacliflow prevention assembly or double check assembly or double
check or DC shall mean an assembly which consists of two independently acting, approved
check valves, including tightly closing resilient seated shutoff valves attached at each end of the
assembly and fitted with properly located resilient seated test cocks.
Fire-line tester shall mean a tester who is employed by a state approved fire-line
contractor and is qualified to test backflow prevention assemblies on fire-lines only.
General tester shall mean a tester who is qualified to test backflow prevention assemblies
on any domestic, commercial, industrial or irrigation service except fire-lines.
Mobile unit shall mean any operation, which may have the potential to introduce
contaminants into a potable water system from a mobile source. These include, but are not
limited to, carpet-cleaning vehicles, water-hauling vehicles, street-cleaning vehicles, liquid-waste
vehicles, power-wash operations and pest-control vehicles.
Nonresidential use shall mean water used by any person other than a residential customer
of the water supply and include all uses not specifically included in "residential uses" as defined
in the city zoning ordinance.
Point-of-use isolation shall mean the appropriate backflow prevention within the
consumer's water system at the point at which the actual or potential cross connection exists.
Page 4
TM 171Ib.7b.IJIJIJ
Potable water supply shall mean any water supply intended or used for human consumption or
other domestic use.
Premises isolation shall mean the appropriate backflow prevention at the servIce
connection between the public water system and the water user.
Pressure vacuum breaker backflow prevention assembly or pressure vacuum breaker or
PVB shall mean an assembly which provides protection against backsiphonage, but does not
provide adequate protection against backpressure backflow. The assembly is a combination of a
single check valve with an A VB and can be used with downstream resilient seated shutoff
valves. In addition, the assembly has suction and discharge gate valves and resilient seated test
cocks which allows the full testing of the assembly.
Public water system or system shall mean any public or privately owned water system,
which supplies water for public domestic use. The system will include all services, reservoirs,
facilities, and any equipment use in the process of producing, treating, storing, or conveying
water for public consumption.
Reduced pressure principle bacliflow prevention assembly or reduced pressure principle
assembly or RP assembly or RP shall mean an assembly containing two independently acting
approved check valves together with a hydraulically-operated, mechanically independent
pressure differential relief valve located between the check valves and at the same time below
the first check valve. The assembly shall include properly located resilient seated test cocks and a
tightly closing resilient seated shutoff valve at the end of the assembly.
Reduced pressure principle detector bacliflow prevention assembly or reduced pressure
detector or RPDA shall mean an assembly composed of a line-size approved reduced pressure
principle assembly with a bypass containing a specific water meter and an approved reduced
pressure principle backflow prevention assembly. The meter shall register accurately for very
low rates of flow.
Representative of the water system shall mean a person approved by the city to perform
cross connection control duties that shall include, but are not limited to, cross connection
inspections and water use surveys.
Residential use shall mean water used by any residential customer of the water supply
and include home owners' associations, single family dwellings, duplexes, triplexes, and
apartments where the individual units are each on a separate meter; or, in cases where two or
more units are served by one meter, the units are full-time dwellings.
Service connection shall mean the point of delivery which the water purveyor loses
control of the water.
Spill-resistant pressure vacuum breaker or SVB shall mean an assembly containing an
independently operating, internally loaded check valve and independently operating, loaded air
inlet valve located on the discharge side of the check valve. This assembly is to be equipped with
Page 5
T\11711b.7b.IJIJIJ
a properly located resilient seated test cock and tightly closing resilient seated shutoff valves
attached at each end of the assembly.
TCEQ shall mean the Texas Commission on Environmental Quality.
Tester shall mean a person that is a certified backflow prevention assembly technician
approved by and registered with the city and the TCEQ.
Thermal expansion shall mean heated water that does not have the space to expand.
Used water shall mean water supplied by a public water system to a water user's system
after it has passed through the service connection.
Water use survey shall mean a survey conducted or caused to be conducted by the local
authority designed to identify any possible sources of contamination to the potable water supply.
Sec. 12-152. Cross connections standards.
Every source of contamination or possible contamination from any contaminant which
originates from or is located at a residential or commercial establishment, which is connected to
any public water supply or which provides water to the public shall be equipped with the
protection required under the provisions of this article.
Sec. 12-153. Right-of-way encroachment.
No person shall install or maintain a backflow prevention assembly upon or within any
city rights-of-way except as provided in this section.
(1) A backflow prevention assembly required by the city may be installed upon or within
any city rights-of-way only if the owner proves to the city that there is no other
feasible location for installing the assembly, installing it in the rights-of-way will not
interfere with traffic or utilities, and obtains a permit from the city. The city retains
the right to approve the location, height, depth, enclosure, and other requisites of the
assembly, prior to its installation.
(2) All permits and inspections required by the Code of Ordinances to perform work in
the rights-of-way shall be obtained.
(3) The assembly shall be installed below or flush with the surrounding grade except
when it is not practicable to install it in this manner. Any assembly or portion of an
assembly, which extends aboveground, shall be located no closer than 18 inches to
the face ofthe curb.
(4) The city shall not be liable for any damage done to or caused by an assembly installed
in a right-of-way.
Page 6
TlI I7l1b.7b.IJIJIJ
(5) A property owner shall, at the request of the city and at the owner's expense, relocate
a backflow prevention assembly which encroaches upon any city rights-of-way when
such relocation is necessary for street or utility construction or repairs for purposes of
public safety.
(6) A person commits an offense if he fails to relocate a backflow prevention assembly
located in or upon any city rights-of-way after receiving a written order from the
regulatory authority.
Sec. 12-154. Multiple connections.
Any premises requiring multiple service connections for adequacy of supply and/or fire
protection will be required to install a backflow assembly on each of the additional service lines
to the premises. The type of assembly will be determined by the degree of hazard that could
occur in the event of an interconnect between any of the buildings on the premises.
Sec. 12-155. Protection required; installation.
(a) All back flow prevention assemblies installed after October 7, 2002 shall be installed
in a manner designed to facilitate ease of inspection by an approved tester. The backflow
prevention assembly protection which is required under this article shall be any of the duly
nationally recognized and authorized backflow prevention assemblies listed in a state approved
plumbing code. Failure to install a backflow prevention assembly as authorized by state
approved plumbing code may result in the backflow prevention assembly failing to meet final
approval by the regulatory authority. The city shall determine the type and location of backflow
assembly to be installed within the area served by the city. The backflow prevention assembly
shall be required in each of the following circumstances, but is in no way limited to the
following:
(1) The nature and extent of any activity on the premises, or the materials used in
connection with any activity on the premises, or materials stored on the premises,
could contaminate or pollute the potable water supply.
(2) Premises having anyone or more cross connections and such cross connection is
protected by an atmospheric vacuum breaker device.
(3) Internal cross connections are present that are not correctable.
(4) Intricate plumbing arrangements that are present which make it impractical to
ascertain whether cross connections exist.
(5) There is unduly restricted entry so that inspections for cross connections cannot
be made with sufficient frequency to assure that cross connections do not exist.
(6) Installation of an approved backflow prevention assembly is deemed to be
necessary to accomplish the purpose of these regulations in the judgment of the
city.
Page 7
T\11711Ub.IJIJIJ
(7) An appropriate cross connection survey report form has not been filed with the
building inspections department of the city of the colony upon request of the city.
(8) A fire suppression system that is connected to the city's water system.
(9) All new construction, if deemed necessary in the system plan review. The type of
assembly required will be determined by the degree of hazard.
(10) When a building is constructed on commercial premises, and the end use of such
building is not determined or could change, a reduced pressure principle backflow
prevention assembly may be installed at the service connection that supplies water
for public domestic use.
(11) Any used water return system.
(12) In the event a point-of-use assembly has not had the testing or repair done as
required by this article, a premises isolation assembly will be required.
(13) If it is determined that additions or alterations have been made to the plumbing
system without obtaining proper permits, premises isolation may be required.
(14) All multistory buildings or any building with a booster pump or elevated storage
tank.
(15) Retrofitting will be required on all high hazard connections and wherever else the
city deems necessary to retrofit.
(b) All backflow prevention assemblies installed after October 7,2002 shall be installed
in a manner designed to facilitate ease of inspection by an approved tester. Any currently
installed backflow prevention assemblies which are located in inaccessible locations or where the
tester is subject to physical danger shall be relocated to approved locations following current
national guideline standards.
Sec. 12-156. Testing of assemblies.
(a) All commercial backflow prevention assemblies shall be caused to be inspected and
the test report must be filed with the City in each of the following circumstances:
( I) Immediately after installations;
(2) Whenever the assembly is moved;
(3) A minimum of once a year;
(4) Premises that have been vacated and unoccupied for one year, prior to re-occupancy;
Page 8
TlI \711 b.7b.IJIJIJ
(5) Immediately after repairs.
(b) All residential backflow prevention assemblies shall be caused to be inspected and
the test report must be filed with the City in each of the following circumstances:
(1) Immediately after installations;
(2) Whenever the assembly is moved;
(3) Immediately after repairs.
All assembly testing shall be performed by a state certified backflow prevention assembly tester,
approved by the regulatory authority.
(c) Duly authorized employees of the city bearing proper credentials and identification
are entitled to enter any public or private property at any reasonable time for the purpose of
enforcing this article. Persons and occupants of premises which are provided water service by the
city, either directly or indirectly, shall allow the city or its representatives ready access at all
reasonable times to all parts of the premises for the purposes of inspection, testing, records
examination, or in the performance of any of their duties. Where persons or occupants of
premises have security measures in force which would require proper identification and
clearance before entry into their premises, the persons and occupants of the premises shall make
necessary arrangements with their security guards so that upon presentation of suitable
identification, personnel from the city will be permitted to enter, without delay, for the purposes
of performing their specific responsibilities.
(d) The city is not liable for damage to a backflow prevention assembly, which may
occur during testing.
(e) A water use survey may be conducted at any establishment located in the city which
is served by a public water supply or which provides water to the public. Upon determination
that the establishment falls under the provisions of this article and requires a backflow prevention
assembly, a notice to abate the condition or to install the proper backflow prevention assembly
shall be issued.
(f) It is the responsibility of the person who owns or controls property to have all
assemblies tested in accordance with this article. Assemblies may be required to be tested more
frequently if the city or state or any agents thereof deem necessary.
(g) All results from assembly testing by a certified backflow prevention assembly tester
shall be placed on a form that is purchased by the tester from the city for an established fee.
Sec. 12-157. Thermal expansion.
It is the responsibility of any person who owns or controls property to eliminate the
possibility of thermal expansion, if a closed system has been created by the installation of a
backflowassembly.
Page 9
T\11711b.7b.IJIJIJ
Sec. 12-158. Pressure loss.
Any reduction in water pressure caused by the installation of a backflow assembly is not
the responsibility of the city.
Sec. 12-159. Residential service connections.
Any person who owns or controls any residential property which has been determined to
have an actual or potential cross connection will be required to eliminate the actual or potential
cross connection or have an approved backflow assembly installed in accordance with this
article.
Sec. 12-160. Rental properties.
Any person who owns or controls property is responsible for the installation, testing and
repair of all backflow assemblies on their property.
Sec. 12-161. Customer service inspection.
(a) Pursuant to TCEQ water system regulations, a customer service inspection for cross
connection control shall be completed by the city prior to providing continuous water service in
each of the following circumstances:
(1) Water service to a newly constructed facility or previously nonexisting premises.
(2) After any material improvement to building(s) or premises.
(3) Any correction or addition to the plumbing of any facility or premises.
(4) The city deems it necessary.
(b) Permanent water service shall not be supplied to a new construction facility( s) until
after the customer service inspection is completed.
(c) Temporary water service which poses a potential cross connection threat to the
potable water supply shall be protected by an approved backflow prevention assembly.
Sec. 12-162. Installation guidelines and requirements for backflow prevention assemblies.
(a) General. To ensure proper operation and accessibility of all backflow prevention
assemblies, the following national guideline requirements shall apply to the installation of these
assemblies.
(1) Backflow prevention assemblies shall be installed in accordance with the current
TCEQ rule and these regulations. The assembly installer must obtain the required
Page 10
T\117l1 b.7b.OOO
plumbing permits and be a certified backflow prevention assembly technician
approved and registered with the city and the TCEQ.
(2) At facilities which require a backflow prevention assembly to be installed at the
point of delivery of the water supply, such installation of the assembly must be
before any branch in the line and on private property located just inside the
boundary between the city rights-of-way and the landowner's property. The city
may specify other areas for installation of the assembly. Assemblies that must be
installed or are located on city rights-of-way are the responsibilities of the
individual, business or entity that the water line is serving.
(3) The assembly must be protected from freezing and other severe weather
conditions.
(4) All backflow prevention assemblies shall be of a type and model approved by the
city.
(5) All vertical installations of backflow assemblies must have prior approval by the
city.
(6) Assemblies that are larger than four inches and installed more than five feet above
floor level must have a suitable platform for use by testing or maintenance
personnel.
(7) Bypass lines are prohibited. Pipe fittings which could be used for connecting a
bypass line must not be installed.
(8) Premises where an uninterrupted water supply is critical shall be provided with
two assemblies installed in parallel. They shall be sized in such a manner that
either assembly will provide the maximum flow required.
(9) Lines shall be thoroughly flushed prior to installation. A strainer with blowout
tapping may be required ahead of the assembly.
(10) All facilities that require continuous, uninterrupted water service and are required
to have a backflow assembly must make provisions for the parallel installation of
assemblies of the same type so that testing, repair and maintenance can be
performed.
(11) The property owner assumes all responsibility for any damages resulting from
installation, operation, and/or maintenance of a backflow assembly. The owner
shall be responsible for keeping all backflow prevention assembly vaults
reasonably free of silt and debris.
(12) Upon completion of installation, the city shall be notified and all assemblies must
be inspected and tested. All assemblies must be registered with the city and shall
Page 11
nll7llb.7b.1I1I11
provide the date of installation, manufacturer, model, type, size, serial number of
the backflow assembly, and initial test report.
(b) Reduced pressure principle bacliflow prevention assemblies (RP). Reduced pressure
principle backflow prevention assemblies may be utilized at premises where a substance is
handled that would be hazardous to health if introduced into the potable water system. The RP is
normally used in locations where an air gap is impractical. The RP shall be effective against both
backsiphonage and backpressure.
(1) RP's must be sized to provide an adequate supply of water and pressure for the
premises being served. Flow characteristics are not standard. The manufacturer's
specifications shall be consulted for specific performance data.
(2) The assembly must be readily accessible for testing and maintenance and must be
located in an area where water damage to building or furnishing would not occur
from relief valve discharge. The property owner assumes all responsibility for any
damage caused by water discharge from an RP assembly. An approved air gap
shall be located at the relief valve orifice ofRP assemblies.
(3) No part of a reduced pressure principle backflow prevention assembly shall be
submerged in water or installed in a location subject to flooding. RP's are
typically installed above grade in well drained areas, but may be installed below
grade (ground level) if a boresight drain to daylight, is provided. The drain shall
be of adequate capacity to carry the full rated flow of the assembly and shall be
screened on both ends.
(4) Enclosures shall be designed for ready access and sized to allow for the minimum
clearances established below. Removable protective enclosures are typically
installed on the smaller assemblies. Daylight drain ports must be provided to
accommodate full pressure discharge from the assembly.
(5) Assemblies two inches and smaller shall have at least a six-inch clearance on both
sides and on top of the assembly, and 12 inches below and behind the assembly.
All assemblies larger than two inches shall have a minimum of 12 inches on the
back side, 24 inches on the test cock side, and the relief valve opening shall be at
least 12 inches plus nominal size of the assembly above the floor or highest
possible water level. Headroom of six feet is required in vaults without a fully
removable top. A minimum access opening of 36 inches is required on all vault
lids.
(6) All RP assemblies must be tested in accordance with this article. Tests are the
responsibility of the assembly owner. The owner must notify the city upon
installation of any backflow prevention assembly.
(7) Variances from these specifications will be evaluated on a case-by-case basis.
Any deviations must have prior written approval of the city.
Page 12
T\117I1b.7b.1I1I1I
(c) Reduced pressure principle detector backflow prevention assemblies (RPDA).
Reduced pressure principle detector backflow prevention assemblies (RPDA) may be utilized in
all installations requiring a reduced pressure principle backflow prevention assembly and
detector metering.
(1) RPDA's shall comply with the installation requirements applicable for reduced
pressure principle backflow assemblies (RP).
(2) The line-size RP assembly and the bypass RP assembly must each be tested. A
separate test report for each assembly must be completed by the certified tester.
(d) Double check valve bacliflow prevention assemblies (DC). Double check valve
backflow prevention assemblies (DC) may be utilized at premises where a substance is handled
that would be objectionable but not hazardous to health if introduced into the potable water
system.
( I) DC's must be sized to provide an adequate supply of water and pressure for
premises being served. Consult manufacturer's specifications for specific
performance data.
(2) Premises where an uninterrupted water supply is critical shall be provided with
two assemblies installed in parallel. Assemblies shall be sized in such a manner
that either assembly will provide the minimum water requirements while the two
together will provide the maximum flow required.
(3) The assembly shall be readily accessible with adequate room for testing and
maintenance. DC's may be installed below grade, providing all test cocks are
fitted with brass pipe plugs. All vaults shall be well drained, constructed of
suitable materials, and sized to allow for the minimum clearances established
below.
(4) Assemblies two inches and smaller shall have at least six-inch clearance below
and on both sides of the assembly, and if located in a vault, the bottom of the
assembly shall be not more than 24 inches below grade. All assemblies larger than
two inches shall have a minimum clearance of 12 inches on the back side, 24
inches on the test cock side, and 12 inches below the assembly. Headroom of six
feet is required in vaults without a fully removable top. A minimum access
opening of 36 inches is required on all vault lids. "Y" pattern double check valve
assemblies shall be installed so that the checks are horizontal and the test cocks
face upward. These clearance standards apply to all assemblies installed in vaults,
enclosures, and meter boxes.
(5) Vertical installations of DC's are allowed only on sizes up to and including four
inches that meet the following requirements:
a. Internally spring-loaded check valves;
Page 13
TlI171Ib.76.11\111
b. Flow is upward through the assembly;
c. Manufacturer states their assembly can be used in a vertical position;
d. Approved by the building official or his designee.
(6) All DC's must be tested in accordance with this article. Tests are the responsibility
of the assembly owner. The owner must notify the regulatory authority upon
installation of any backflow prevention assembly.
(7) Variances from these specifications will be evaluated on a case-by-case basis.
Any deviations must have prior written approval of the city.
(e) Double check detector bacliflow prevention assemblies (DCDA). Double check
detector backflow prevention assemblies (DCDA) may be utilized in all installations requiring a
double check valve assembly and detector metering.
(1) DCDA's shall comply with the installation requirements applicable for double
check valve assemblies (DCs).
(2) The line-size DC assembly and the bypass DC assembly must each be tested. A
separate test report for each assembly must be completed by the certified tester.
(f) Pressure vacuum breaker bacliflow prevention assemblies (PVB). Pressure vacuum
breaker backflow prevention assemblies (PVB) may be utilized at point-of-use protection only
and where a substance is handled that would be objectionable but not hazardous to health if
introduced into the potable water system. PVB's protect against backsiphonage only and shall not
be installed where there is potential for backpressure.
(1) Assembly shall be installed a minimum of 12 inches above highest downstream
pIpmg.
(2) PVB's shall not be installed in an area subject to flooding or where damage would
occur from water discharge.
(3) The assembly shall be readily accessible for testing and maintenance, with a
minimum clearance of 12 inches all around the assembly.
(4) All PVB's must be tested in compliance with this article. Tests are the
responsibility of the assembly owner. The owner must notify the regulatory
authority regarding installation of any backflow prevention assembly.
(5) Variances from these specifications will be evaluated on a case by case basis. Any
deviations must have prior written approval of the regulatory authority.
(g) Spill resistant pressure vacuum breaker bacliflow prevention assemblies (SVB).
Spill resistant pressure vacuum breaker backflow prevention assemblies (SVB) may be utilized
in all installations requiring a pressure vacuum breaker.
Page 14
TlI 17116.7(1.1)1111
(I) SVB's shall comply with the installation requirements applicable for pressure
vacuum breaker backflow prevention assemblies.
Sec. 12-163. Air gap separation.
Air gaps provide maximum protection from backflow hazards and shall be utilized at all
locations where high hazardous substances are at risk of entering the potable water system.
(1) An air gap separation shall be at least twice the diameter of the supply pipeline
measured vertically above the top rim of the receiving vessel and in no case less
than one inch. If splashing is a problem, tubular screens may be attached or the
supply line may be cut at a 45-degree angle. The air gap distance is measured
from the bottom of the angle. Hoses are not allowed.
(2) Air gap separations shall not be altered in any way without prior approval from
the regulatory authority and must be available for inspection at all reasonable
times.
(3) Side walls, ribs or similar obstructions do not affect air gaps when spaced from
the inside edge of the spout opening to a distance greater than three times the
diameter of the effective opening for a single wall, or a distance greater than four
times the effective opening for two intersecting walls.
Sec. 12-164. Fire suppression systems.
All new installations of a fire suppression system which utilize the city's potable water
supply shall have installed an approved backflow prevention device, according to the degree of
hazard.
An approved double check detector backflow prevention assembly (DCDA) or reduced
pressure detector assemblies (RPDA) shall be the minimum protection for fire sprinkler systems
using piping material that is not approved for potable water use and/or that does not provide for
periodic flow-through during each 24-hour period, unless a variance has been issued in writing
from the city. An RPDA must be installed if any solution other than the potable water can be
introduced into the sprinkler system.
(I) It is the responsibility of all property owners and persons in charge of any
premises to abide by the conditions of this article. In the event of any changes to
the plumbing system, it is the responsibility of the property owners to notify the
regulatory authority. All costs associated with this article and the purchase,
installation, testing and repair of a DCDA or RPDA device is the responsibility of
the property owner and persons in charge of any premises.
(2) Upon the approved installation of the DCDA or RPDA device, a cross connection
test report completed by a licensed fire-line tester must be sent to the attention of
the city and shall include the information required by this article.
Page 15
T.\11711b.7b.IHHI
Sec. 12-165. Fire hydrant protection.
An approved double check device backflow prevention assembly (DCD) or reduced
pressure detector assemblies (RPDA) shall be the minimum protection for fire hydrant water
meters which are being used for a temporary water supply during any construction or other uses
which would pose a potential hazard to the public water supply. An RPDA must be installed if
any solution other than the potable water can be introduced into the sprinkler system.
(1) It is the responsibility of all persons engaging in the use and rental of a fire
hydrant water meter to abide by the conditions of this article. All fire hydrant
water meter rentals shall meet the current requirements as provided for by the
city.
(2) Only City of The Colony fire hydrant water meters with approved backflow
prevention assemblies are allowed to be used within the city limits.
(3) A refundable deposit is required to insure the return of all water meter and
backflow assemblies to the city. Failure to return the assemblies can result in the
forfeiture of deposit and/or enforcement action being taken against the responsible
party, as allowed for in the penalty section of this article.
(4) All nonapproved fire hydrant meters which are found to be in use in the city will
be confiscated and enforcement action taken against the responsible party, as
allowed for in the enforcement section in this article.
Sec. 12-166. Responsibilities of property owner clause.
(a) It is the responsibility of all property owners and/or persons in charge of any
premises to abide by the conditions of this article and to comply with the following:
(I) Payment of all costs associated with this article and the purchase, installation,
testing and repair of backflow prevention assemblies.
(2) Install and maintain all backflow prevention assemblies in accordance with this
article and acceptable industry practice.
(3) Test all commercial backflow prevention assemblies on their premises annually.
Such testing of all commercial establishments must be conducted by a certified
backflow prevention assembly tester who is registered with the City of The
Colony.
(4) Maintain all backflow prevention assemblies in proper working order at all times,
including repair, as required.
(5) Maintain all backflow prevention assemblies in a manner which allows them to be
tested by a method that has been approved by the City of The Colony.
Page 16
TlI 17ll6.7b.000
(6) Retain all records related to backflow prevention assembly installation, testing
and repair for a minimum of five (5) years.
(b) Certified bacliflow prevention assembly tester. Shall comply with the following
requirements:
(1) Annually register with the City of The Colony and pay the required fee.
(2) Maintain testing equipment in proper working condition/calibration.
(3) Maintain the design or operation characteristics of the approved assembly.
(4) Ensure that devices are tested according to accepted industry practice and TCEQ
regulations.
(5) Enter required testing data, including test gauge serial numbers, on cross
connection test forms obtained from the City of The Colony.
(6) Provide a copy of the completed test report to the City of The Colony within ten
(10) business days of testing for all low hazard assemblies and within three (3)
business days for all high hazard assemblies. The degree of hazard will be
determined by the type of application device and table provided for in the most
recently adopted International Plumbing Code.
(7) Provide a copy of the completed test report to the property owners and/or persons
in charge of any premises. Completed test reports submitted to the City of The
Colony after the required time must pay double the required fee. Completed test
reports submitted more than thirty (30) days late must be retested and the tester
must pay double the required fee.
(8) Maintain testing and/or repair records for a minimum of five (5) years.
Sec. 12-167. Backflow prevention assembly tester certification--Registration required.
Only approved TCEQ licensed backflow prevention assembly testers can test backflow
prevention assemblies in the city. Testers must register annually with the city, provide proof of
TCEQ certification, and provide proof that testing equipment is able to maintain a calibration of
plus or minus two-tenths (0.2) psid accuracy, and pay an annual, nonrefundable, tester
registration fee.
Sec. 12-168. Fees.
(a) There shall be an annual, nonrefundable, tester registration fee in accordance with
the approved resolution. Such fee can be amended from time to time at the desire of the city
council.
(b) There shall be a nonrefundable registration fee for each nonresidential backflow
prevention assembly device for new installation and replacement. An annual nonresidential
Page 17
T\117l1 b.7b.000
backflow prevention assembly device shall be charged thereafter. Such fee can be amended, by
resolution, from time to time at the desire of the city council.
(c) There shall be a testing fee for each separate backflow prevention assembly on
which a test is performed, as required by the city. If upon inspection or testing of a newly
installed backflow prevention assembly it is deemed not to be working properly, it is the
responsibility of the property owners and/or persons in charge of any premises to make necessary
repairs.
Sec. 12-169. Compliance for lawn irrigation.
For all lawn irrigation system installations a permit shall be required. Such permit shall
be issued by the building inspection department. Installation requirements must comply with the
current city plumbing code and or guidelines for the appropriate device found in this article.
Interconnections of the potable water supply with an alternate water source are prohibited unless
appropriate backflow protection is installed. High hazard backflow protection devices must be
installed if any mechanical injection stations are used with the irrigation system.
Sec. 12-170. Mobile units.
The connection of a mobile unit to any potable water system is prohibited unless such
connection is protected by an air gap or an approved backflow prevention assembly. Prior
approval and annual device testing of any backflow prevention assembly must be received from
the city before connecting to any potable water system.
Sec. 12-171. Enforcement.
(a) Official. This article shall be enforced by the building official, or his designated
representative.
(b) Testing of backflow prevention assemblies. The city shall require to be tested all
backflow prevention assemblies by a licensed tester, pursuant to the requirements of this article.
(1) For new facilities, permanent water service shall not be provided until all
backflow prevention assemblies have been tested and are operational. Except in
cases where the testing of backflow prevention assemblies must be delayed until
the installation of internal production or auxiliary equipment, the regulatory
authority shall not approve a certificate of occupancy until all backflow
prevention assemblies have been tested and are operational. The city shall not be
liable for damage caused to any backflow prevention assembly as a result of the
inspection or testing.
(2) Failure to have backflow prevention assemblies tested within the required
timeframe may result in the city testing, or causing the testing, of such device.
The city reserves the right to disconnect water service to any property in lieu of
testing.
(c) Violations.
Page 18
T\11711b.7b.OOO
(1) A person commits an offense if there is failure to maintain backflow prevention
assemblies in compliance with this section.
(2) A person commits an offense if there is failure to comply with a repair order
issued by the city.
(3) A person commits an offense if backflow from premises owned, operated or
managed by the person enters the public water supply system.
(4) A person commits an offense if there is a failure to pay any fees required by this
article.
(5) A person commits an offense by violating any section of this article.
(6) A person commits an offense if discontinued or disconnected water service to
premises under this article is reinstated except as directed by the city.
(7) A person in charge of any facility commits an offense by allowing an unregistered
tester to perform testing work at their establishment.
(8) A person commits an offense by testing a backflow prevention assembly within
the city without being registered with the regulatory authority.
(9) A person commits an offense by testing a backflow prevention assembly within
the city without being certified by the TNRCC.
(d) Penalty.
(1) A person who violates any provision of this article is guilty of a misdemeanor and
upon conviction is punishable by any remedy accorded by law, each act of
violation and for each day or part of a day during which the violation is
committed, continued or permitted.
(2) In addition to proceeding under the authority of subsection (d)(I) of this section,
the city is entitled to pursue all other criminal and civil remedies to which is
entitled under the authority of statutes or other ordinances against a person
committing any violation of this article including injunction and civil penalties.
(3) In addition to (d)(I) and (d)(2) above, a civil penalty of a fine not to exceed one
hundred fifty and nollOO Dollars ($150.00) may be imposed for any violation of
the provisions of this ordinance.
(e) Sanction for failure to pay inspection fees. In addition to sanctions provided for by
this article, the city is entitled to exercise sanctions provided for by other ordinances of the city.
(f) Review and revocation of tester's registration. A certified tester's registration may be
reviewed and revoked by the city if it is determined that the tester:
(I) Has falsely, incompletely, or inaccurately reported assembly reports;
Page 19
T\11711b.7b.000
(2) Has used inaccurate gauges;
(3) Has used improper testing procedures; or
(4) Has created a threat to public health or the environment.
Secs. 12-172--12-190. Reserved."
SECTION 2. If any section, article paragraph, sentence, clause, phrase or word in this
ordinance, or application thereto any persons or circumstances is held invalid or unconstitutional by
a Court of competent jurisdiction, such holding shall not affect the validity of the remaining portions
of this ordinance; and the City Council hereby declares it would have passed such remaining
portions of this Ordinance despite such invalidity, which remaining portions shall remain in full
force and effect.
SECTION 3: That all provisions of the Ordinances of the City of The Colony, Texas, in
conflict with the provisions ofthis ordinance be, and the same are hereby amended, repealed, and all
other provisions of the Ordinances of the City not in conflict with the provisions of this ordinance
shall remain in full force and effect.
SECTION 4. Any person, firm, or corporation violating any of the provisions of this
ordinance shall be deemed guilty of a misdemeanor and, upon conviction in the municipal court
of the City of The Colony, Texas, shall be punished by a fine not to exceed the sum of Five
Hundred Dollars ($500.00) for each offense. Every day a violation occurs shall constitute a
separate offense.
SECTION 5. This Ordinance shall become effective from and after its date of passage in
accordance with law.
PASSED AND APPROVED BY THE CITY COUNCIL OF THE CITY OF THE
COLONY, TEXAS THIS 4th day of June 2007.
~
Robert E. Hager, C
(REH/cdb OS/29/07)
Page 20
1'\11711 b.7b.000