Loading...
HomeMy WebLinkAboutOrdinance No. 06-1629 THE CITY OF THE COLONY, TEXAS ORDINANCE NO. ~ (p - I ~..2 q AN ORDINANCE OF THE CITY OF THE COLONY, TEXAS AMENDING THE CODE OF ORDINANCES BY AMENDING CHAPTER 9, ARTICLE I, SECTION 9-2, BY DELETING ALL REFERENCES TO THE INTERNATIONAL FIRE CODE, 2000 EDITION, AND THE AMENDMENTS THERETO AND PROVIDING FOR THE ADOPTION OF THE INTERNATIONAL FIRE CODE, 2003 EDITION; PROVIDING AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2003 EDITION; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A REPEALING CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING A PENALTY FOR VIOLATION OF THIS ORDINANCE NOT TO EXCEED THE SUM OF TWO THOUSAND DOLLARS ($2,000.00) FOR EACH OFFENSE; AND PROVIDING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF THE COLONY, TEXAS: SECTION 1. That the Code of Ordinances of the City of The Colony, Texas be, and the same is, hereby amended by amending Chapter 9, Article I, Section 9-2, by deleting all references to the International Fire Code, 2000 Edition and the amendments thereto and providing for the adoption the International Fire Code, 2003 Edition, and the amendments thereto, which shall read as follows: "ARTICLE 1. IN GENERAL Sec. 9-2. Fire code; adopted. (a) Adoption by reference. The International Fire Code, 2003 Edition, as published by the International Code Council is hereby adopted by reference. Unless deleted, amended, expanded or otherwise changed herein, all provisions of such Code shall be fully applicable and binding. Any and all references to the NFP A Codes shall mean the most current edition available, as amended. (b) Amendments. (1) Section 102.4; change to read as follows: 102.4 Application of other codes. The design and construction of new structures shall comply with this code, and other codes as applicable. Page 1 79754 Repairs, alterations and additions to existing structures shall comply with this code and the International Building Code. (2) Section 102.6; change to read as follows: 102.6 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFP A 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. (3) *Section 202; amend definition of Fire Watch as follows: FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. (4) Section 202; add a new definition to read as follows: HIGH-RISE BUILDING. A building having any floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access. (5) Section 202; add definitions as follows: SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief. When utilized, the number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally calculated by the jurisdiction. (6) Section 307.2; change to read as follows: 307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burning. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Page 2 79754 Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the following: 1. Texas Commission on Environmental Quality guidelines and/or restrictions. 2. State, County or Local temporary or permanent bans on open burning. 3. Local written policies as established by the Code Official. (7) Section 307.3; change to read as follows: 307.3 Location. The location for open burning shall not be less than 300 feet (91 440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91 440 mm) of any structure. Exceptions not changed. (8) Add Section 307.3.3 to read as follows: 307.3.3 Trench Bums. Trench bums shall be conducted in air curtain trenches and in accordance with Section 307.2. (9) Section 307.4; change to read as follows: 307.4 Attendance. Open burning, trench bums, bonfires or recreational fires shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with Section 906 with a minimum 4-A rating or other approved on-site fire-extinguishing equipment, such as dirt, sand, water barrel, garden hose or water truck, shall be available for immediate utilization. (10) Section 308.3.1; change to read as follows: 308.3.1 Open-flame cooking devices. Charcoal burners and other open- flame cooking devices shall not be operated or located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system. (11) Section 308.3.1.1; change to read as follows: 308.3.1.1 Liquefied-petroleum-gas- fueled cooking devices. When permitted as listed in the exceptions of Section 308.3.1, LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds Page 3 79754 [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exception: One- and two-family dwellings, and other residential occupancies when those residential occupancies are in compliance with Section 308.3.1, exception #2, may have containers with a water capacity not greater than 20 pounds (9.08 kg) [nominal 1 pound (0.454 kg) LP-gas capacity]. (12) Section 401.3.2 to read as follows: 401.3.2 Alarm Activations. Upon activation of a fire alarm signal, employees or staff shall immediately notify the fire department. All occupants of that facility shall follow their fire department approved evacuation plan or immediately evacuate the facility. (13) Section 405.1; change to read as follows: 405.1 General. Emergency evacuation drills complying with the provisions of this section shall be conducted in the occupancies listed in Table 405.2 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities. (14) Section 408.5.4; change to read as follows: 408.5.4 Drill frequency. Emergency evacuation drills shall be conducted at least twelve times per year, four times per year on each shift. (15) Section 503.1.1; add the following sentence to the first paragraph: Except for single- or two-family residences, the path of measurement shall be along a minimum ofa ten feet (10') wide unobstructed pathway around the external walls of the structure. (16) Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315mm), except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4267 mm). Exception: Vertical clearance may be reduced; provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. (17) Section 503.2.2; change to read as follows: 503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. Page 4 79754 (18) Section 503.3; change to read as follows: 503.3 Marking. Approved striping or, when allowed by the code official, signs, or both, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs and striping shall be maintained in a clean and legible condition at all times and is replaced or repaired when necessary to provide adequate visibility. (1) Striping - Fire apparatus access roads shall be marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the stripping shall be on the vertical face of the curb. (2) Signs - Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet (50') apart. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief. (19) Section 503.4; change to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times. (20) Section 704.1; change to read as follows: 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoist ways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as specified in Table 704.1. When openings are required to be protected, openings into such shafts shall be maintained self-closing by smoke detection. Existing fusib1e-link-type automatic door-closing devices are permitted if the fusible link rating does not exceed 1350F (570C). (21) Section 803.3.2 and Section 803.4.2; add an exception to read as follows: Page 5 79754 Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. (22) Section 804.1.1; add a second exception to read as follows: Exceptions: 1. Trees located in areas protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 shall not be prohibited in Groups A, E, M, R-l and R-2. 2. Trees shall not be prohibited inside private dwelling units of Group R-2 Occupancies. (23) Section 901.7; change to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the code official shall be notified immediately and, where required by the code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. (24) Section 902.1; under "Standpipe, Types of' definition, amend "Manual dry" by adding a sentence to read as follows: The system must be supervised as specified in Section 905.2. (25) Section 903.2; delete the exception. Exception: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided those spaces or areas are equipped throughout with an automatic fire alarm system and are separated from the remainder of the building by a wall with a fire-resistance rating of not less than 1 hour and a floor/ceiling assembly with a fire-resistance rating of not less than 2 hours. (26) Add Section 903.2.8.3 to read as follows: 903.2.8.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Exception: One-story self-service storage facilities that have no interior corridors, with a one-hour fire barrier separation wall installed between every storage compartment. (27) Section 903.2.10; amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5, and 903.2.10.6 as follows: Page 6 79754 903.2.10.3 Buildings more than 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the International Building Code, that is located 35 feet (10 668mm) or more above the lowest level of fire department vehicle access. Exception: 1. Open parking structures in compliance with Section 406.3 of the International Building Code. 903.2.10.4 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 23 to determine if those provisions apply. 903.2.10.5 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire- extinguishing system. 903.2.10.6 Buildings Over 6,000 sq.ft. An automatic sprinkler system shall be installed throughout all buildings with a building area over 6,000 sq.ft. For the purpose of this provision, fire walls shall not define separate buildings. Exceptions: 1. Open parking garages in compliance with Section 406.3 of the International Building Code. 2. Type A-5. (28) Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt locations. When approved by the code official, automatic sprinklers shall not be required in the following rooms or areas where such are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. Page 7 79754 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. (29) Section 903.3.5; add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. (30) Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (31) Add Section 903.6.2 to read as follows: 903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 1504. (32) Section 905.2; changed to read as follows: 905.2 Installation Standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm. (33) Section 905.3.2; delete exceptions #1 and #2. Exceptions: 1. Open-air-seating spaces without enclosed spaces. 2. Class I automatic dry and semiautomatic dry standpipes or manual wet standpipes are allowed in buildings where the highest floor surface used for human occupancy is 75 feet (22 860 mm) or less above the lowest level of fire department vehicle access. (34) Section 905.4, item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located either on the roof or at the highest landing of stairways with stair access to the roof. An additional hose Page 8 79754 connection shall be provided at the top of the most hydraulically remote standpipe for testing purposes. (35) Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (36) Add Section 907.1.3 to read as follows: 907.1.3 Design Standards. All alarm systems new or replacement serving 50 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 75 smoke detectors or more than 200 total alarm activating devices shall be analog intelligent addressable fire detection systems. Exception: Existing systems need not comply unless the total building remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building must comply within 18 months of permit application. (37) Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. (38) Section 907.2.3; change exception #1 and add exception #1.1 to read as follows: 1. Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1 Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. Page 9 79754 (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) (39) Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings having any floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communications system in accordance with Section 907.2.12.2. (40) Section 907.2.12, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seating; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. (41) Section 907.4; add a second paragraph to read as follows: Manual alarm actuating devices shall be an approved double action type. (42) Add Section 907.6.1 to read as follows: 907.6.1 Installation. All fire alarm systems shall be installed in such a manner that the failure of any single alarm-actuating or alarm-indicating device will not interfere with the normal operation of any other such devices. All systems shall be Class "A" wired with a minimum of six feet separation between supply and return loops. IDC - Class "A" style - D - SLC Class "A" Style 6 - notification Class "B" Style Y. (43) Section 907.9.2; change to read as follows: 907.9.2 High-rise buildings. In buildings that have any floor located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access that are occupied for human occupancy, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: 1. Smoke detectors 2. Sprinkler water-flow devices 3. Manual fire alarm boxes 4. Other approved types of automatic fire detection devices or suppression systems (44) Section 1008.1.3.4; replace #3 to read as follows 3. The doors shall be arranged to unlock by panic hardware. Page 10 79754 (45) Section 1008.1.3.4; add criteria #7 as follows: 7. If a full building smoke detection system is not provided, approved smoke detectors shall be provided on both the access and egress sides of doors and in a location approved by the authority having jurisdiction of NFP A 72. Actuation of a smoke detector shall automatically unlock the door. (46) Section 1016.1; add an exception number 5, which shall read asfollows: 5. In Group B office buildings, corridor walls and ceilings need not be of fire-resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic smoke-detection system within the corridor. The actuation of any detector shall activate alarms audible in all areas served by the corridor. The smoke-detection system shall be connected to the building's fire alarm system where such a system is provided. (47) Section 1019.1.8; change to read as follows: 1019.1.8 Smoke proof enclosures. In buildings required to comply with Section 403 or 405, each of the exits of a building that serves stories where any floor surface is located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access or more than 30 feet (9144 mm) below the level of exit discharge serving such floor levels shall be a smoke proof enclosure or pressurized stairway in accordance with Section 909.20 of the International Building Code. (48) Section 1504.6; change to read as follows: 1504.6 Fire Protection. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system complying with Chapter 9 which shall also protect exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used. (49) Section 2302; add a second paragraph to the definition of "High-Piled Combustible Storage" to read as follows: Any building exceeding 6,000 sq.ft. that has a clear height in excess of 12 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall comply with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities, to the maximum pile height. (50) Section 2703.1.5 shall be added to read asfollows: 2703.1.5 Hazardous Materials Storage Is Prohibited In Residential Occupancies. Page 11 79754 Exception. Quantities are permitted for the maintenance of pertinent equipment of systems for such uses and shall be in accordance with Chapter 27. (51) Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays, storage and handling of fireworks as provided in Section 3304 and 3308. 2. The use of fireworks for approved display as permitted in Section 3308. (52) Section 3302; change the definition of "fireworks" to read as follows: FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of lAG fireworks or 1.3G fireworks as set forth herein. (53) Section 3403.6; add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. (54) Section 3404.2.11.5; add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. (55) Section 3404.2.11.5.2; change to read as follows: 3404.2.11.5.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFP A 30 and as specified in Section 3404.2.11.5.3. (56) Add Section 3404.2.11.5.3 to read as follows: 3404.2.11.5.3 Dry sumps. Approved sampling tubes of a minimum 6 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the comers of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation Page 12 79754 and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. (57) Section 3404.3.4.2 to read as follows: 3404.3.4.2 Group R occupancies: Quantities in Group R occupancies shall not exceed that necessary for maintenance purposes and operation of equipment and shall not exceed 20 U.S. gallons. (58) Delete Section 3406.5.4.5 and replace with the following: 3406.5.4.5 Commercial, industrial, governmental or manufacturing. Dispensing of Class II and III motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, governmental or manufacturing establishments is allowed where permitted, provided such dispensing operations are conducted in accordance with Sections 3406.5.4.5.1 through 3406.5.4.5.3. 3406.5.4.5.1 Site requirements. 1. Dispensing may occur at sites that have been permitted to conduct mobile fueling. 2. A detailed site plan shall be submitted with each application for a permit. The site plan must indicate: a. all buildings, structures, and appurtenances on site and their use or function; b. all uses adjacent to the property lines of the site; c. the locations of all storm drain openings, adjacent waterways or wetlands; d. information regarding slope, natural drainage, curbing, impounding and how a spill will be retained upon the site property; and, e. The scale of the site plan. 3. The Code Official is authorized to impose limits upon: the times and/or days during which mobile fueling operations are allowed to take place and specific locations on a site where fueling is permitted. 4. Mobile fueling operations shall be conducted in areas not generally accessible to the public. 5. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or combustible storage. 3406.5.4.5.2 Refueling Operator Requirements. 1. The owner of a mobile fueling operation shall provide to the jurisdiction a written response plan which demonstrates readiness to respond to a Page 13 79754 fuel spill, carry out appropriate mitigation measures, and to indicate its process to properly dispose of contaminated materials when circumstances require. 2. The tank vehicle shall comply with the requirements ofNFPA 385 and Local, State and Federal requirements. The tank vehicle's specific functions shall include that of supplying fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good repmr. 3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the point of fueling shall be prominently posted on 3 sides ofthe vehicle including the back and both sides. 4. A fire extinguisher with a minimum rating of 40:BC shall be provided on the vehicle with signage clearly indicating its location. 5. The dispensing nozzles and hoses shall be of an approved and listed type. 6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48m) in length. 7. Absorbent materials, non-water absorbent pads, a 10 foot (3.048 m) long containment boom, an approved container with lid, and a non- metallic shovel shall be provided to mitigate a minimum 5-gallon fuel spill. 8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limiting the amount of a single fueling operation to a maximum of 500 gallons (1893 L) between resetting of the limit switch. Exception: Tankers utilizing remote emergency shut-off device capability where the operator constantly carries the shut-off device which, when activated, immediately causes flow of fuel from the tanker to cease. 9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating actions in the event of a fire, leak, or spill. Training records shall be maintained by the dispensing company and shall be made available to the Code Official upon request. 10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an emergency communications device to notify the proper authorities in the event of an emergency. Page 14 79754 3406.5.4.5.3 Operational Requirements. 1. The tank vehicle dispensing equipment shall be constantly attended and operated only by designated personnel who are trained to handle and dispense motor fuels. 2. Prior to beginning dispensing operations, precautions shall be taken to assure ignition sources are not present. 3. The engines of vehicles being fueled shall be shut off during dispensing operations. 4. Night time fueling operations shall only take place in adequately lighted areas. 5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude traffic from driving over the delivery hose and between the tank vehicle and the motor vehicle being fueled. 6. During fueling operations, tank vehicle brakes shall be set, chock blocks shall be in place and warning lights shall be in operation. 7. Motor vehicle fuel tanks shall not be topped off. 8. The dispensing hose shall be properly placed on an approved reel or in an approved compartment prior to moving the tank vehicle. 9. The Code Official and other appropriate authorities shall be notified when a reportable spill or unauthorized discharge occurs. (59) Add Section 3803.2.1.8 to read as follows: 3803.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. (60) Section 3804.2; add an exception #2 to read as follows: Exception: 2. Except as permitted in 308.3 and 3804.3.2, LP-gas containers are not permitted in residential areas. (61) Add Section 3804.3.2 to read as follows: Page 15 79754 3804.3.2 Spas, Pool Heaters and other listed devices. Where natural gas service is not available, LP-Gas containers are allowed to be used to supply spa and pool heaters or other listed devices. Such containers shall not exceed 250-gallon water capacity. See Table 3804.3 for location of containers. " SECTION 2. That in the event a conflict exists between any two (2) Codes adopted by the City of The Colony the most restrictive provision shall apply. SECTION 3. If any section, subsection, paragraph, sentence, phrase or work in this ordinance, or application thereof to any person or circumstance is held invalid by any court of competent jurisdiction, such holding shall not affect the validity of the remaining portions of this ordinance, and the City Council of the City of The Colony, Texas hereby declares it would have enacted such remaining portions despite any such invalidity. SECTION 4. That the repeal of any ordinance or any portion thereof by the preceding sections shall not affect or impair any act done or right vested or accrued or any proceeding, suit or prosecution had or commenced in any cause before such repeal shall take effect; but every such act done, or right vested or accrued, or proceedings, suit or prosecution had or commenced shall remain in full force and effect to all intents or purposes as if such ordinance or part thereof so repealed shall remain in force. SECTION 5. That any person, firm or corporation violating any of the provisions of this ordinance or the Code of Ordinances as amended hereby, shall be guilty of a misdemeanor and upon conviction in the Municipal Court of the City of The Colony, Texas, shall be subject to a fine not to exceed the sum of Two Thousand Dollars ($2,000.00) for each offense; and each and every day such offense is continued shall constitute a new and separate offense. SECTION 6. That this ordinance shall become effective immediately from and after its passage and the publication of the caption, as the law and charter in such cases provide. PASSED AND APPROVED by the City Council of the City of The Colony, TexaS,thisthe~daYOf~~/ ,2006. Page 16 79754 ATT~ C~eWilS~n~i~T~ S TO FORM: Robert E. Hager City Attorney (REH/cdb 1/9/06) Page 17 79754