HomeMy WebLinkAboutOrdinance No. 05-1628
CITY OF THE COLONY, TEXAS
ORDINANCE NO. 05- 1""< 8
AN ORDINANCE OF THE CITY OF THE COLONY, TEXAS
AMENDING THE CODE OF ORDINANCES BY AMENDING
CHAPTER 6, ARTICLE I, SECTION 6-2(a), BY DELETING ALL
REFERENCES TO THE NATIONAL ELECTRICAL CODE, 1999
EDITION, AND THE AMENDMENTS THERETO AND
PROVIDING FOR THE ADOPTION OF THE NATIONAL
ELECTRIC CODE, 2005 EDITION; AND, BY AMENDING
SECTION 6-3, SAME-AMENDMENTS, BY REPEALING ALL
AMENDMENTS TO THE 1999 NATIONAL ELECTRICAL CODE
AND REPLACING THE SAME WITH THE AMENDMENTS TO
THE NATIONAL ELECTRICAL CODE, 2005 EDITION;
PROVIDING A SEVERABILITY CLAUSE; PROVIDING A
REPEALING CLAUSE; PROVIDING A SAVINGS CLAUSE;
PROVIDING A PENAL TY FOR VIOLATION OF THIS
ORDINANCE NOT TO EXCEED THE SUM OF TWO THOUSAND
DOLLARS ($2,000.00) FOR EACH OFFENSE; AND PROVIDING
AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF THE
COLONY, TEXAS:
SECTION 1. That the Code of Ordinances of the City of The Colony, Texas be,
and the same is, hereby amended by amending Chapter 6, Article I, Section 6-2(a), by
deleting all references to the National Electrical Code, 1999 Edition and providing for the
adoption the National Electrical Code, 2005 Edition, which shall read as follows:
"ARTICLE 1. IN GENERAL
Sec. 6-2. Electrical code - Adopted.
(a) Title; adoption. The title of this section is "The City of The Colony
Electrical Code." It may be cited as such, and it is referred to in this section as "this
code." The National Electrical Code, 2005 Edition, as published by the National
Fire Protection, is hereby adopted by reference as the electrical code of the city,
subject to all amendments and conflicting provisions contain in this Code or
ordinances. A true and correct copy of said National Electrical Code shall be kept in
the office of the city secretary and be made available for inspection during regular
business hours.
Page 1
79782
Sec. 6-3. Same - Amendments.
The following are hereby adopted as amendments to the National Electrical
Code ("NEC") adopted herein, and such amendments shall be and become a part of
the code as adopted:
Section 230.71 (A) add an exception.
230.71 Maximum Number of Disconnects.
(A) General. The service disconnecting means for each service permitted by 230.2,
or for each set of service-entrance conductors permitted by 230.40, Exception Nos.
1,3,4, or 5, shall consist of not more than six switches or sets of circuit breakers,
mounted in a single enclosure, in a group of separate enclosures, or in or on a
switchboard. There shall be no more than six sets of disconnects per service
grouped in anyone location. For the purpose of this section, disconnecting means
used solely for power monitoring equipment, transient voltage surge suppressors, or
the control circuit of the ground-fault protection system or power-operable service
disconnecting means, installed as part of the listed equipment, shall not be
considered a service disconnecting means.
Exception: Multi-occupant Buildings. Individual service disconnecting means is
limited to six for each occupant. The number of individual disconnects at one
location may exceed six.
Section 300.11 add an exception.
300.11 Securing and Supporting.
(A) Secured in Place. Raceways, cable assemblies, boxes, cabinets, and fittings
shall be securely fastened in place. Support wires that do not provide secure
support shall not be permitted as the sole support. Support wires and associated
fittings that provide secure support and that are installed in addition to the ceiling
grid support wires shall be permitted as the sole support. Where independent
support wires are used, they shall be secured at both ends. Cables and raceways
shall not be supported by ceiling grids.
Exception: Ceiling grid support wires may be used for structural supports when
the associated wiring is located in that area, not more than two raceways or cables
supported per wire, with a maximum nominal metric designation 16 (trade size
Yz").
Section 310. 15(B)(6) change to read as follows:
310.15 Ampacities for Conductors Rated 0-2000 Volts.
(B) Tables.
Page 2
79782
(6) 120/240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders. For
dwelling units, conductors, as listed in Table 310.15(B)(6), shall be permitted as
120/240-volt, 3-wire, single-phase service-entrance conductors, service lateral
conductors, and feeders conductors that serve as the main power feeder to each
dwelling unit and are installed in raceway or cable with or without an equipment
grounding conductor. For applications of this section, the main disconnect and the
lighting and appliance branch-circuit panel boards. The feeder conductor shall be
permitted to be smaller than the ungrounded conductors, provided the requirements
of215.2, 220.61, and 230.42 are met. This Section shall not be used in conjunction
with 220.82.
Section 500.8(A)(1) change to read as follows:
500.8 Equipment.
(A) Approval for Class and Properties.
(1) Equipment shall be identified not only for the class oflocation but also for the
explosive, combustible, or ignitable properties of the specific gas, vapor, dust,
fiber, or flyings that will be present. In addition , Class I equipment shall not
have any exposed surface that operates at a temperature in excess of the ignition
temperature of the specific gas or vapor. Class II equipment shall not have an
external temperature higher than that specified in 500.8(C)(2). Class III
equipment shall not exceed the maximum surface temperatures specified in 503.1.
FPN: Luminaries (lighting fixtures) and other heat-producing apparatus,
switches, circuit breakers, and plugs and receptacles are potential sources of
ignition and are investigated for suitability in classified location. Such types of
equipment, as well as cable terminations for entry into explosion proof
enclosures, are available as listed for Class I, Division 2 locations. Fixed wiring,
however may utilize wiring methods that are not evaluated with respect to
classified locations. Wiring products such as cable, raceways, boxes, and fittings,
therefore, are not marked as being suitable for Class I, Division 2 locations. Also
see Exception No.3 to 500.8(B).
"
SECTION 2. If any section, subsection, paragraph, sentence, phrase or work in
this ordinance, or application thereof to any person or circumstance is held invalid by any
court of competent jurisdiction, such holding shall not affect the validity of the remaining
portions of this ordinance, and the City Council of the City of The Colony, Texas hereby
declares it would have enacted such remaining portions despite any such invalidity.
SECTION 3. That the repeal of any ordinance or any portion thereof by the
preceding sections shall not affect or impair any act done or right vested or accrued or
Page 3
79782
any proceeding, suit or prosecution had or commenced in any cause before such repeal
shall take effect; but every such act done, or right vested or accrued, or proceedings, suit
or prosecution had or commenced shall remain in full force and effect to all intents or
purposes as if such ordinance or part thereof so repealed shall remain in force.
SECTION 4. That any person, firm or corporation violating any of the
provisions of this ordinance or the Code of Ordinances as amended hereby, shall be
guilty of a misdemeanor and upon conviction in the Municipal Court of the City of The
Colony, Texas, shall be subject to a fine not to exceed the sum of Two Thousand Dollars
($2,000.00) for each offense; and each and every day such offense is continued shall
constitute a new and separate offense.
SECTION 5. That this ordinance shall become effective immediately from and
after its passage and the publication of the caption, as the law and charter in such cases
provide.
PASSED ~ND APPRO]D by the Cit.y Council of the City of The Colony,
this the ~ day of. ~ &2.. ,2005.
Texas,
~L
. Ai. N~~
stie Wilson, City Secretary
, City Attorney
~ (REH/cdb .lJ/f.~05L ,
'-YWl.bM. \-;3E:{~
Page 4
79782